Certifications, standards & evidence

Which regulation applies to which system, who is allowed to install it and what evidence must end up in the file — this website's complete catalogue of standards and intervals on one page.

At a glance.

Preventive fire protection is not governed by a single law but by a web of them: product standards for the components, application standards for planning and operation, workplace rules for use, state building regulations and inspection ordinances for the duty, and insurance directives for cover. That is precisely where gaps come from — not from negligence, but because hardly anyone has every source in view at once.

This page brings together what is otherwise spread across the service pages: every regulation we work to, with an indication of which trades it affects — and beneath that, every inspection interval on this website in a single list. It is intended as a working tool: for the inspection visit, for the tender, for the conversation with the insurer.

A note on terminology, because it is often confused here: the standards listed are the regulations that planning, installation, acceptance and maintenance are carried out to. They are not awards a company holds. Where a trade requires a specialist company qualification — DIN 14675 for fire alarm systems, for instance — we evidence the qualifications required for your project before any commission is placed.

  • Complete catalogue of the standards and regulations applied
  • Every inspection and maintenance interval in one overview
  • Each regulation mapped to the trades it affects
  • A basis for tendering, inspection visits and insurance discussions
  • Evidence of the required qualifications before any commission is placed

Kenndaten

Leitnorm
Regelwerke
Regulations in the catalogue
44
Regelwerke
44
Prüfpunkte
27

Standards & regulations.

The rules this work is planned, installed, signed off and maintained against.

DIN 14675
Standard 01 / 44

Fire alarm systems — Design and operation

Governs planning, design, installation, commissioning, acceptance and maintenance. Requires a specialist firm with appropriately qualified personnel. Applies to: Fire alarm systems, Voice alarm systems.

DIN VDE 0833-1
Standard 02 / 44

Hazard alarm systems — General requirements

Basis for the operation and maintenance of all hazard alarm systems. Applies to: Fire alarm systems.

DIN VDE 0833-2
Standard 03 / 44

Requirements for fire alarm systems

Detector selection, monitoring scope and the triggering of other equipment. Applies to: Fire alarm systems.

DIN EN 54
Standard 04 / 44

Fire detection and fire alarm systems — Component standards

Requirements for control panels, detectors, alarm devices and power supply. Applies to: Fire alarm systems.

DIN 14676
Standard 05 / 44

Smoke alarms for residential buildings

Planning, installation, operation and maintenance of smoke alarms in residential premises. Applies to: Fire alarm systems.

DIN EN 14604
Standard 06 / 44

Smoke alarms — Product standard

Product requirements for the device itself. Applies to: Fire alarm systems.

Landesbauordnung
Standard 07 / 44

Smoke alarm obligation under state law

The smoke alarm obligation is a matter for the federal states. In Berlin it applies to residential units; owners are responsible for installation. Applies to: Fire alarm systems.

DIN VDE 0833-4
Standard 08 / 44

Voice alarm systems for use in case of fire

Governs the planning, installation, operation and maintenance of voice alarm systems and their interaction with the fire alarm system. Applies to: Voice alarm systems.

DIN EN 54-16
Standard 09 / 44

Voice alarm control and indicating equipment

Product requirements for the control panel that stores, monitors and outputs alarm announcements. Applies to: Voice alarm systems.

DIN EN 54-24
Standard 10 / 44

Loudspeakers for voice alarm systems

Product standard for the loudspeakers themselves, including their behaviour in case of fire. Applies to: Voice alarm systems.

DIN EN 54-4
Standard 11 / 44

Power supply equipment

Requirements for the power supply unit and battery backup — a voice alarm system must remain able to make announcements even during a power outage. Applies to: Voice alarm systems.

DIN EN 50849
Standard 12 / 44

Electroacoustic emergency warning systems

Applies to emergency warning systems beyond the pure fire case; it superseded DIN EN 60849. Applies to: Voice alarm systems.

MLAR
Standard 13 / 44

Muster-Leitungsanlagen-Richtlinie

Requires cabling for safety-relevant systems to maintain circuit integrity for a defined period, so that the announcement does not fail along with the cable in case of fire. Applies to: Voice alarm systems.

Sonderbauvorschriften
Standard 14 / 44

Requirements under state law

Whether a voice alarm system is required follows from the fire safety concept and the state's special building regulations — for example for assembly, retail and accommodation premises. Applies to: Voice alarm systems.

DIN 18232
Standard 15 / 44

Smoke and heat control

Design and execution of smoke extraction systems; basis for the required vent area. Applies to: Smoke & heat extraction.

DIN EN 12101-2
Standard 16 / 44

Natural smoke and heat exhaust ventilators (NSHEV)

Product requirements for naturally operating devices. Applies to: Smoke & heat extraction.

DIN EN 12101-3
Standard 17 / 44

Powered smoke and heat exhaust ventilators

Requirements for fans used in powered smoke extraction. Applies to: Smoke & heat extraction.

VdS 2098
Standard 18 / 44

Guidelines for smoke and heat extraction systems

Supplementary requirements from the property insurers' perspective. Applies to: Smoke & heat extraction.

DIN 14677
Standard 19 / 44

Maintenance of hold-open systems

Requires recurring maintenance by a competent person and its documentation. Applies to: Hold-open systems.

DIBt-Zulassung
Standard 20 / 44

General building authority approval

Hold-open systems require approval. Only approved combinations of components may be installed. Applies to: Hold-open systems.

DIN EN 14637
Standard 21 / 44

Electrically controlled hold-open systems

Product requirements for hold-open systems for fire and smoke doors. Applies to: Hold-open systems.

DIN 4102-5
Standard 22 / 44

Fire-resistant closures — Terminology and requirements

Basis for the T30, T60 and T90 classification. Applies to: Fire doors.

DIN 4102-18
Standard 23 / 44

Fire-resistant closures — Verification

Requirements for the proof of usability. Applies to: Fire doors.

DIN EN 1634-1
Standard 24 / 44

Fire resistance tests for door assemblies

European test method for determining the fire resistance duration. Applies to: Fire doors.

DIN EN 16034
Standard 25 / 44

Fire and smoke control door and shutter sets — Product standard

Performance characteristics for CE marking. Applies to: Fire doors.

DIN 18095
Standard 26 / 44

Smoke control doors

Requirements for smoke-tight closures. Applies to: Fire doors.

DIN EN 1838
Standard 27 / 44

Applied lighting technology — Emergency lighting

Illuminance levels, uniformity and rated operating duration for escape routes and anti-panic lighting. Applies to: Emergency lighting.

DIN VDE 0108-100
Standard 28 / 44

Emergency lighting systems

Installation and operation in buildings where people gather. Applies to: Emergency lighting.

DIN EN 50172
Standard 29 / 44

Emergency lighting systems — Operation

Governs testing, test intervals and logbook records. Applies to: Emergency lighting.

ASR A3.4/3
Standard 30 / 44

Emergency lighting and safety guidance systems

Arbeitsstättenregel — binding for workplaces. Applies to: Emergency lighting.

DIN 4844
Standard 31 / 44

Safety signage

Design and use of escape route signs. Applies to: Emergency lighting.

DIN VDE 0833-3
Standard 32 / 44

Requirements for intrusion and hold-up alarm systems

Operation and maintenance of intrusion alarm systems. Applies to: Intruder protection.

DIN EN 50131
Standard 33 / 44

Alarm systems — Intrusion and hold-up systems

Defines security grades 1 to 4 and the associated requirements. Applies to: Intruder protection.

VdS 2311
Standard 34 / 44

Planning and installation of intrusion alarm systems

Guideline of the property insurers; often a precondition for insurance cover. Applies to: Intruder protection.

DIN EN 62676
Standard 35 / 44

Video surveillance systems

Requirements for system performance and image quality. Applies to: Intruder protection.

DSGVO
Standard 36 / 44

General Data Protection Regulation (GDPR)

Video surveillance processes personal data: the legal basis, retention period and notice obligation must be clarified without exception. Applies to: Intruder protection.

DIN 14406-4
Standard 37 / 44

Portable fire extinguishers — Maintenance

Requires recurring maintenance by a qualified person and specifies what is inspected and documented. Usual interval: two years. Applies to: Fire extinguishers.

DIN EN 3
Standard 38 / 44

Portable fire extinguishers — Product standard

Construction, extinguishing capacity, labelling and fire classes of the device itself. Applies to: Fire extinguishers.

ASR A2.2
Standard 39 / 44

Measures against fire

Determines, via extinguishing units, how many fire extinguishers a workplace needs, and regulates accessibility and fire wardens. Applies to: Fire extinguishers.

ASR A1.3
Standard 40 / 44

Safety and health signage

Specifies how fire extinguisher locations must be marked so they can be found in an emergency. Applies to: Fire extinguishers.

DIN EN ISO 7010
Standard 41 / 44

Graphical symbols — Safety signs

Source of the F001 fire safety sign for fire extinguishers. Applies to: Fire extinguishers.

BetrSichV
Standard 42 / 44

Betriebssicherheitsverordnung

CO₂ extinguishers are pressure equipment and are additionally subject to a recurring inspection of the pressure vessel. Applies to: Fire extinguishers.

DIN 14096
Standard 43 / 44

Brandschutzordnung

Parts A, B and C — the wall notice, instruction of building occupants and duties for staff with special fire safety responsibilities. Applies to: Fire extinguishers.

DGUV Information 205-023
Standard 44 / 44

Fire wardens

Describes the training, number and duties of the fire wardens a company should appoint. Applies to: Fire extinguishers.

From survey to maintenance.

  1. 01

    Site survey

    Record every existing system, inspection report and maintenance contract — including the ones nobody has so far felt responsible for.

  2. 02

    Comparison against the regulations

    Establish for each system which standards and deadlines apply, and where what is installed departs from them.

  3. 03

    Defect and deadline list

    Rank the deviations by urgency: what must be put right immediately, what by the next appointment, what merely needs documenting.

  4. 04

    Retrofitting & acceptance

    Add what is missing, have the systems accepted and bring the evidence together in one place.

  5. 05

    Deadline management

    Keep every interval in one plan and give notice in good time before it expires.

Inspect, maintain, document.

What has to be inspected how often — and the standard each interval rests on.

quarterly
Inspection 01 / 27

Fire alarm systems: Inspection of the system

  • DIN VDE 0833-1
annually
Inspection 02 / 27

Fire alarm systems: Maintenance of the system

  • DIN VDE 0833-1
annually
Inspection 03 / 27

Fire alarm systems: Functional test of smoke alarms

  • DIN 14676
after 10 years
Inspection 04 / 27

Fire alarm systems: Replacement of smoke alarms

  • DIN 14676
quarterly
Inspection 05 / 27

Voice alarm systems: Inspection of the system

  • DIN VDE 0833-1
annually
Inspection 06 / 27

Voice alarm systems: Maintenance of the system

  • DIN VDE 0833-1
annually
Inspection 07 / 27

Voice alarm systems: Test of the emergency power supply

  • DIN EN 54-4
at acceptance and after modifications
Inspection 08 / 27

Voice alarm systems: Verification of speech intelligibility

  • DIN VDE 0833-4
annually
Inspection 09 / 27

Smoke & heat extraction: Functional test of the complete system

  • DIN 18232 / manufacturer's specification
semi-annually
Inspection 10 / 27

Smoke & heat extraction: Visual inspection of openings and actuators

  • Operator's duty
as required by state law
Inspection 11 / 27

Smoke & heat extraction: Inspection by an expert

  • State inspection ordinance
annually
Inspection 12 / 27

Hold-open systems: Maintenance by a competent person

  • DIN 14677
monthly
Inspection 13 / 27

Hold-open systems: Visual check of function and wedging

  • Operator's duty
annually
Inspection 14 / 27

Fire doors: Functional and closing test

  • Manufacturer's specification / operator's duty
monthly
Inspection 15 / 27

Fire doors: Visual check that the door closes unobstructed

  • Operator's duty
annually
Inspection 16 / 27

Fire doors: Inspection of self-closing devices

  • Building code law
monthly
Inspection 17 / 27

Emergency lighting: Short-duration functional test

  • DIN EN 50172
annually
Inspection 18 / 27

Emergency lighting: Test of rated operating duration

  • DIN EN 50172
monthly
Inspection 19 / 27

Emergency lighting: Visual inspection of escape route signs

  • Operator's duty
quarterly
Inspection 20 / 27

Intruder protection: Inspection of the system

  • DIN VDE 0833-1
annually
Inspection 21 / 27

Intruder protection: Maintenance of the system

  • DIN VDE 0833-1
annually
Inspection 22 / 27

Intruder protection: Review of retention periods and camera fields of view

  • GDPR accountability obligation
regularly
Inspection 23 / 27

Fire extinguishers: Visual check of accessibility and condition

  • Operator's duty, ASR A2.2
every two years
Inspection 24 / 27

Fire extinguishers: Maintenance by a qualified person

  • DIN 14406-4
every ten years
Inspection 25 / 27

Fire extinguishers: Pressure vessel inspection of CO₂ extinguishers

  • BetrSichV
annually
Inspection 26 / 27

Fire extinguishers: Instruction of employees

  • DGUV Vorschrift 1
upon change of use
Inspection 27 / 27

Fire extinguishers: Recalculation of extinguishing units

  • ASR A2.2

What you get.

Benefit 01 / 03

One source instead of eight

Standards and deadlines for every trade in one place — rather than scattered across product data sheets, maintenance contracts and ring binders.

Benefit 02 / 03

Gaps become visible

Comparing what is installed against the regulations shows which system has been running without valid evidence, and since when.

Benefit 03 / 03

Demonstrable to third parties

The authority, the insurer and the employers' liability insurance association do not ask about the system, they ask for the evidence. That is exactly what this produces.

Questions.